1、防火卷簾控制器應進行通電功能、備用電源、火災報警功能、故障報警功能、自動控制功能、手動控制功能和自重下降功能調試,并應符合下列要求:
1. The fire shutter controller should be debugged for power on function, backup power supply, fire alarm function, fault alarm function, automatic control function, manual control function, and self weight lowering function, and should meet the following requirements:
(1)通電功能調試時,應將防火卷簾控制器分別與消防控制室的火災報警控制器或消防聯動控制設備、相關的火災探測器、卷門機等連接并通電,防火卷簾控制器應處于正常工作狀態。
(1) When debugging the power on function, the fire shutter controller should be connected and powered on to the fire alarm controller or fire linkage control equipment in the fire control room, relevant fire detectors, door rolling machines, etc. The fire shutter controller should be in normal working state.
檢查數量:全數檢查。
Inspection quantity: All inspections.
檢查方法:直觀檢查。
Inspection method: Visual inspection.
(2)備用電源調試時,設有備用電源的防火卷簾,其控制器應有主、備電源轉換功能。主、備電源的工作狀態應有指示,主、備電源的轉換不應使防火卷簾控制器發生誤動作。備用電源的電池容量應保證防火卷簾控制器在備用電源供電條件下能正常可靠工作1h,并應提供控制器控制卷門機速放控制裝置完成卷簾自重垂降,控制卷簾降下限位所需的電源。
(2) When debugging the backup power supply, the controller of the fire resistant roller shutter equipped with the backup power supply should have the function of switching between the main and backup power supplies. The working status of the main and backup power supplies should be indicated, and the conversion of the main and backup power supplies should not cause the fire shutter controller to malfunction. The battery capacity of the backup power supply should ensure that the fire resistant roller shutter controller can operate normally and reliably for 1 hour under the backup power supply conditions, and the controller should be provided to control the speed release control device of the roller shutter machine to complete the weight drop of the roller shutter and control the power supply required to lower the roller shutter to the lower limit.
檢查數量:全數檢查。
Inspection quantity: All inspections.


檢查方法:切斷防火卷簾控制器的主電源,觀察電源工作指示燈變化情況和防火卷簾是否發生誤動作。再切斷卷門機主電源,使用備用電源供電,使防火卷簾控制器工作1h,用備用電源啟動速放控制裝置,觀察防火卷簾動作、運行情況。
Inspection method: Cut off the main power supply of the fireproof roller shutter controller, observe the changes in the power indicator light and whether the fireproof roller shutter has malfunctioned. Cut off the main power supply of the rolling door machine again, use a backup power supply to power the fire shutter controller for 1 hour, start the quick release control device with the backup power supply, and observe the action and operation of the fire shutter.
(3)火災報警功能調試時,防火卷簾控制器應直接或間接地接收來自火災探測器組發出的火災報警信號,并應發出聲、光報警信號。
(3) When debugging the fire alarm function, the fire shutter controller should directly or indirectly receive the fire alarm signal from the fire detector group, and should emit sound and light alarm signals.
檢查數量:全數檢查。
Inspection quantity: All inspections.
檢查方法:使火災探測器組發出火災報警信號,觀察防火卷簾控制器的聲、光報警情況。
Inspection method: Make the fire detector group emit a fire alarm signal, and observe the sound and light alarm of the fire shutter controller.
(4)故障報警功能調試時,防火卷簾控制器的電源缺相或相序有誤,以及防火卷簾控制器與火災探測器之間的連接線斷線或發生故障,防火卷簾控制器均應發出故障報警信號。
(4) When debugging the fault alarm function, if the power supply of the fire shutter controller is out of phase or has incorrect phase sequence, as well as the connection line between the fire shutter controller and the fire detector is broken or malfunctioning, the fire shutter controller should send a fault alarm signal.
檢查數量:全數檢查。
Inspection quantity: All inspections.
檢查方法:任意斷開電源一相或對調電源的任意兩相,手動操作防火卷簾控制器按鈕,觀察防火卷簾動作情況及防火卷簾控制器報警情況。斷開火災探測器與防火卷簾控制器的連接線,觀察防火卷簾控制器報警情況。
Inspection method: Disconnect one phase of the power supply or switch between any two phases of the power supply, manually operate the button of the fire shutter controller, observe the action of the fire shutter and the alarm of the fire shutter controller. Disconnect the connection wire between the fire detector and the fire shutter controller, and observe the alarm status of the fire shutter controller.
(5)自動控制功能調試時,當防火卷簾控制器接收到火災報警信號后,應輸出控制防火卷簾完成相應動作的信號,并應符合下列要求:
(5) When debugging the automatic control function, when the fire shutter controller receives a fire alarm signal, it should output a signal to control the fire shutter to complete the corresponding action and meet the following requirements:
1)控制分隔防火分區的防火卷簾由上限位自動關閉全閉。
1) The fire roller shutter that controls the partition of the fire compartment automatically closes from the upper limit to the fully closed position.
2)防火卷簾控制器接到感煙火災探測器的報警信號后,控制防火卷簾自動關閉中位(1.8m)處停止,接到感溫火災探測器的報警信號后,繼續關閉全閉。
2) After receiving the alarm signal from the smoke fire detector, the fire shutter controller automatically closes to the middle position (1.8m) and stops. After receiving the alarm signal from the temperature fire detector, it continues to close until fully closed.
3)防火卷簾半降、全降的動作狀態信號應反饋到消防控制室。
3) The action status signals of the fire shutter's half down and full down should be fed back to the fire control room.
檢查數量:全數檢查。
Inspection quantity: All inspections.
檢查方法:分別使火災探測器組發出半陣、全降信號,觀察防火卷簾控制器聲、光報警和防火卷簾動作、運行情況以及消防控制室防火卷簾動作狀態信號顯示情況。
Inspection method: Make the fire detector group emit half array and full down signals respectively, observe the sound and light alarms of the fire roller shutter controller, the action and operation of the fire roller shutter, and the display of the fire roller shutter action status signal in the fire control room.
(6)手動控制功能調試時,手動操作防火卷簾控制器上的按鈕和手動按鈕盒上的按鈕,可控制防火卷簾的上升、下降、停止。
(6) When debugging the manual control function, manually operate the buttons on the fire shutter controller and the buttons on the manual button box to control the rise, fall, and stop of the fire shutter.
檢查數量:全數檢查。
Inspection quantity: All inspections.
檢查方法:手動試驗。
Inspection method: manual test.
(7)自重下降功能調試時,應將卷門機電源設置于故障狀態,防火卷簾應在防火卷簾控制器的控制下,依靠自重下降全閉。
(7) When debugging the self weight lowering function, the power supply of the rolling door machine should be set to a fault state, and the fire shutter should be controlled by the fire shutter controller to lower to fully closed by relying on its self weight.
檢查數量:全數檢查。
Inspection quantity: All inspections.
檢查方法:切斷卷門機電源,按下防火卷簾控制器下降按鈕,觀察防火卷簾動作、運行情況。
Inspection method: Cut off the power supply of the rolling door machine, press the down button of the fire shutter controller, and observe the action and operation of the fire shutter.
感謝您的閱讀,此文的文章來源:濟南卷簾門更多的內容和問題請點 http://www.santoncc.cn我們會繼續努力的為您提供服務,感謝您的支持!
Thank you for reading. The source of this article is Jinan Rolling Shutter Doors. For more information and questions, please click http://www.santoncc.cn We will continue to work hard to provide you with services. Thank you for your support!
下一篇:電動卷閘門故障及維修要注意什么? 上一篇:電動卷簾門的12個小故障排除技巧
閱讀/ Recommended reading
- 濟南卷簾門:如何選擇地下停車場的卷簾門? 2025-04-18
- 挑選快速門有什么要素 2025-04-11
- 鋁合金卷簾門和鐵卷簾門有什么該選擇哪個? 2025-04-10
- 濟南卷簾門如何選購? 2025-03-31
- 濟南卷簾門維修指南 2025-03-25
- 你知道濟南卷簾門是建筑與便捷的守護者嗎? 2025-03-17
- 濟南卷簾門遙控器的配對方法 2025-02-25
- 車庫卷簾門彈簧問題的維修指南 2025-02-22
濟南卷簾門可以在這里定制
2025-04-19
在濟南做卷簾門生意這些年,咱就想著把實實在在的好產品帶給大伙!不管您是商鋪老板、倉庫負責人,還是自建房的住戶,選對卷簾門,不僅守護,還能省心省力,今天就給您嘮嘮咱這兒的卷簾門!...